Intervent
    home        about us        news        products        contact        site map
AXpac
VERTpac
CENTpac
 
 
Vertical Discharge Fans - Intervent VERTpac Range
Vertical Discharge Fans    
Vertical Discharge Fans
 description
Vertical Discharge Mixed Flow roof fan range

- 100% recyclable UV stable materials.
- Ziehl- Abegg motor/impellers fitted
- IP54
- Class F motor insulation
- Thermal motor protection
- Isolation/service switch fitted
- Birdguard fitted
- Range includes 355mm to 500mm

 air flow chart
Vertical Discharge Fans
 technical data 

VERTpac Vertical Discharge Mixed Flow Roof Fan Assemblies

 
m3/s @ Pa
Part Number
rpm
0
25
50
100
150
200
250
300
350
400
Watts
w
S.C
A
F.L.C
A
max
amb
dBA
@ 3m
(Example: VERTpac = Vertical Discharge Mixed Flow Roof fan assy; 355 = dia.mm; 1 = single phase; 4 = 4 pole)
VERTpac 355-14
1410
0.9
0.86
0.8
0.65
0.49
0.22
310
3.7
1.7
60°C
66
VERTpac 355-16
850
0.54
0.44
0.25
92
1.0
0.4
70°C
42
VERTpac 400-14
1320
1.53
1.36
1.3
1.19
1.03
0.82
0.51
520
5.5
2.2
60°C
68
VERTpac 400-16
840
0.92
0.83
0.67
0.35
185
1.2
0.8
50°C
45
VERTpac 450-14
1360
2.16
2.05
1.92
1.8
1.65
1.47
1.28
1.02
0.72
0.28
960
9.6
4.8
40°C
64
VERTpac 450-16
950
1.49
1.44
1.31
1.06
0.67
400
4.7
2.2
55°C
52
VERTpac 500-34
1360
2.88
2.8
2.72
2.53
2.33
2.14
1.9
1.64
1.33
1.0
1350
10
2.3
40°C
66
VERTpac 500-36
910
1.92
1.81
1.67
1.36
0.97
0.34
470
3.7
1.25
40°C
55
 
   
 dimensions

Vertical Discharge Fans

Unit Size (mm)
A
B
C
D
E (max)
F
VERTpac 355
610
675
562
530
100
330
VERTpac 400
610
675
562
530
100
330
VERTpac 450
610
675
562
530
100
330
VERTpac 500
610
675
820
780
100
580
 
    © Copyright 2008 Intervent Group